Quantitative Analysis of Transformer Oil Dissolved Gases Using FTIR
ZHAO An-xin1, 2, TANG Xiao-jun1*, WANG Er-zhen1, ZHANG Zhong-hua1, 3, LIU Jun-hua1
1. Xi’an Jiaotong University State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an 710049, China 2. Xi’an University of Science and Technology, Xi’an 710054, China 3. National Institute of Metrology, Beijing 100013, China
Abstract:For the defects of requiring carrier gas and regular calibration, and low safety using chromatography to on line monitor transformer dissolved gases, it was attempted to establish a dissolved gas analysis system based on Fourier transform infrared spectroscopy. Taking into account the small amount of characteristic gases, many components, detection limit and safety requirements and the difficulty of degasser to put an end to the presence of interference gas, the quantitative analysis model was established based on sparse partial least squares, piecewise section correction and feature variable extraction algorithm using improvement TR regularization. With the characteristic gas of CH4, C2H6, C3H6, and CO2, the results show that using FTIR meets DGA requirements with the spectrum wave number resolution of 1 cm-1 and optical path of 10 cm.
Key words:Fourier transform infrared spectroscopy;Dissolved gas analysis;Quantitative analysis;Sparse partial least squares;On-line monitoring
[1] Singh J, Sood Y R, Jarial R K, et al. IEEE Electrical Insulation Magazine, 2008, 24(3): 11. [2] Singh S, Bandyopadhyay M N. IEEE Electrical Insulation Magazine, 2010, 26(6): 41. [3] SHANG Li-ping,CAO Tie-ze,LIU Xian-yong, et al(尚丽平,曹铁泽,刘先勇, 等). Transformer(变压器), 2004, 41(8):36. [4] Chen W G, Liu B J, Hu J X, et al. Journal of Chongqing University(Natural Science Edition), 2011, 34(2): 7. [5] Chen W G, Liu B J, Huang H X. Sensor Letters, 2011, 9(4): 1511. [6] ZHAO Xiao-xiao,YUN Yu-xin,CHEN Wei-gen(赵笑笑,云玉新,陈伟根). Power System Protection and Control(电力系统保护与控制), 2009, 37(23): 187. [7] CHEN Wei-gen,YUN Yu-xin,PAN Chong, et al(陈伟根,云玉新,潘 翀, 等). Automation of Electric Power Systems(电力系统自动化), 2007, 31(15): 94. [8] LIU Xian-yong,HU Jin-song,ZHOU Fang-jie, et al(刘先勇,胡劲松,周方洁, 等). Transformer(变压器), 2004, 41(10): 33. [9] BAI Peng,LI Yan,ZHANG Bin, et al(白 鹏,李 彦,张 斌, 等). Acta Photonica Sinica(光子学报), 2008, 37(3): 566. [10] HAO Hui-min,QIAO Cong-ming,TANG Xiao-jun, et al(郝惠敏,乔聪明,汤晓君, 等). Journal of Infrared and Millimeter Waves(红外与毫米波学报), 2009, 28(2): 115. [11] TANG Xiao-jun,ZHANG Lei,WANG Er-zhen, et al(汤晓君,张 蕾,王尔珍, 等). Spectroscopy and Spectral Analysis(光谱学与光谱分析), 2012, 32(10): 2730. [12] Bair E, Hastie T, Paul D, et al. Journal of the American Statistical Association, 2006, 101(473): 119. [13] Allegrini F, Olivieri A C. Analytica Chimica Acta, 2011, 699(1): 18.